Warning
Before
using the storage tank, the safety accessories must be assembled with the tank
for air tightness test and do the nitrogen replacement for the tank with a pass
result.
1, Summery
The
horizontal tank is the special equipment used for storage of liquefied
petroleum gas(Lpg) when the saturated vapor pressure is less than 1.77Mpa at
the temperature 50℃ and the safety
storage is 19.95tons. The storage tank is designed according to the TSG 21-2-16
“stationary Pressure Vessels Safety and Technical Supervision Regulation” and
requirements of GB/T 150 “Pressure Vessel”. Manufacturers should have the A2
level manufacturing license issued by the state administration of quality
supervision, inspection and quarantine administration of boiler and pressure
vessel. At any time, the factory should accept the inspection and supervision
by the boiler pressure vessel examination board in local technical supervision
bureau in the process of design, fabrication, inspection, delivery and any
other report with the built drawings, product quality certificate, certificate
of quality, brand extension and design calculation and other technical
information issued by manufacturers should be given to users. Users with the
above date go to register in the local boiler pressure vessel inspection
agencies. Products can be put into use after getting the registration number.
Technical feature:
Design
Standard
《压力容器安全技术监察规程》
“Pressure Vessel Safety Technology and Supervision Code”
《压力容器》
(GB/T150)
“Pressure Vessel”
《卧式容器》(NB/T47042 “Horizontal Vessel”
Other
related rules, regulations and standard, etc.
More pictures of finished surface lpg gas storage tanks customized for overseas clients manufactured by Chengli Special Automobile Co., Ltd. as below.
mini 5,000Liters surface lpg gas storage tank for sale |
20,000Liters surface lpg gas storage tank for sale |
60,000Liters surface lpg gas storage tank for sale |
customized 40,000Liters surface lpg gas storage tank for sale |
CLW brand 45,000Liters surface lpg gas storage tank for sale |
50,000Liters surface lpg gas storage tank for sale |
Website: www.truckdf.com
Mob.: +86 13886878855
Skype: truck0011
Email: szhj9999@163.com
Whatsapp/Wechat: +86 13329899995
QQ: 504873236
Safety accessories adjustment and tank installation
Users
must equip the tanks with safety accessories matching the technical parameters
according to the standard. Safety accessories must conduct re-inspection before
equipping on the tank. Adjusting must follow provisions of general layout
design. Safety accessories installation organization must have related
qualified certificate.
In
tank installation, base surface of the tanks should be not less than 1m above
the ground. Base surface should install base plate. Base installation for
embedded anchor bolts is as below
Base
installation surface should be titled after finish base installation, making
sure the tank will be tilted. The slope is 3/1000. The drain hole is one the
lowest end.
To
keep the tank move freely in axial direction, double nuts are used for locking as
above. After the lower nut was totally tighten firstly, then loose the nuts be
one thread, in this way the base plate can slightly slide in axial direction. In
bolts installation, to make sure each bolts have at least 10mm space to allow
the nuts installation. The stationary saddle should be directly tightened by
nuts. Grounding line on the saddle should be well grounding.
Key point for
equipment safety usage.
Before
LPG filling, tank must be conducted nitrogen replacement to ensure safety. The
oxygen content in the tank must be lower than 3%.
Safety
valves should be tightly closed under normal working conditions. The safety
valve opens automatically when the tank overloads, environment temperature
rises sharply, fire occurs or any other reasons, which makes the tank pressure
exceeds the relief valve sealing pressure. When the safety valve relief
pressure, the relived liquid or gas should be recycled or discharged into the
air through the safety valve outlet pipe.
A
cut off valve should be installed between safety valve and the tank, to prevent
safety valve failure which means it cannot be closed and leads to large
leakages. Then close the cut off valve and replace the safety valve. The
cut-off valve is fully open during normal working and closed only when
replacing the safety valve.
The
seal of the safety valve device shall not be arbitrarily opened, if needs to
re-debug, it must be adjusted by the approval organization by the national
technology supervision agency.
On
pressure gauge dial, a red line should be printed at design pressure value. An
cut-off valve should be installed between pressure gauge and tank. Under normal
working conditions of tank, the valve should be fully open, when replacement or
testing pressure gauge, the cut off valve needs to be closed.
On
magnetic level gauge dial, a redline should be printed at the maximum filling
height. When installation, the tank is completely empty, so the level gauge
should be in zero position. a cut off valve should be installed between the
level gauge and tank, which is fully
open during normal working, only closed the cut off valve in replacement of
magnetic level gauge.
On
temperature gauge dial, a red line should be printed at the design temperature
50℃. Between 40℃ and 50℃, it should be
coated in yellow color.
The
lowest pressure in the tank in the process of using shall not less than
0.05Mpa, which is to prevent the air flow into the tank.
Operation
management and maintenance
Users
of the storage tanks must follow the rules of the “Pressure Vessel Safety and Technical
Supervision Regulation” and other relevant laws and regulations strictly for
safety technology management and prohibit overloading, over temperature and
overpressure to ensure the security usage of the tank.
Technical
director of users us responsible for the pressure vessels safety and technical
management, and specify the professional technical personnel for the daily
technical management of the pressure vessel.
Tank
operations should be tested and approved by the safe education training and get
related certificates.
Cooling
measures must be taken when any of the following circumstance occurs.
a,
the pressure gauge indicating the value gets close to the red line, or the
pressure is keep increasing.
b, the temperature gauge indicate the value reached the yellow warning
signs.
When
the tank pressure meet the design pressure value( the red line indicated value)
and the safety valve does not open, the operator should take immediate measures
to reduce the pressure of the tank first, then close the cut off valve under
safety valve for maintenance calibration, and rapid installation of the safety
valve to let the tank back to normal working condition.
The
storage tank should be tested regularly in accordance with the related rules in
“Pressure Vessel Safety Technology and Supervision Code”.
Chengli Special Automobile Co., Ltd. is the leading manufacturer and supplier of lpg gas pressure vessels in China. With many years’development, Chengli Special Automobile Co., Ltd. can supply surface lpg gas storage tank(5m3-200m3), underground lpg gas storage tank(10m3-80m3), lpg gas trailer(40,5m3-59.6m3), lpg gas truck(5m3-35.5m3), skid lpg gas plant(5-120m3), etc.And in 2016s, we have achieved the US ASME certificate for lpg gas pressure vessels, meaning we can design and mnufacture ASME standard lpg gas pressure vessels in our company and exporting, too. More information, please feel free to contact with Ms. Anita. The hot sale line is 0086 13886878855.